PDU极限值的触发范围
Description :
如果我将PE6108的电流最小值设为0A最大值设为1.8A时,有时候我会看到触发的log讯息,如下:
PDU current (0.000) (Present) minimum threshold warning between 0.2700 ~ 0.0 .
我想知道触发警告讯息的设备范围要如何计算?
Solution :
触发范围(最大极限值 - 最小极限值) x 15%
范例如下:
最大极限值 = 1.8A
最小极限值 = 0.0A
警告触发值为(1.8-0.0) x 15% = 0.27
最小值触发范围 = 0.0 ~ 0.27A
最大值触发范围 = 1.53A ~ 1.8A